電動(dòng)執(zhí)行器的維修和保養(yǎng)(電動(dòng)執(zhí)行器)
發(fā)布時(shí)間:2020-07-28 15:13:13

Common faults and elimination methods of electric actuators

malfunction

the reason

elimination method

1. The motor cannot start

1. Power failure or lack of phase

1. Check the power supply

2. Low power supply voltage

1. Check the voltage

3. The action of the overheat protection switch embedded in the motor coil (motor overheating)

3. See if the fault can be eliminated after the motor temperature drops

4. The valve or actuator itself is stuck

4. Try manual operation with actuator handwheel

2. The motor stops during the switch operation

1. The load is too large, so that the force protection switch acts

1. Try to increase the setting value of torque protection

2. The action of the overheat protection switch embedded in the motor coil (motor overheating)

2. See if the fault can be eliminated after the motor temperature drops

3. Control circuit board failure

3. Replace the circuit board

3. The electrical limit switch cannot limit

1. Motor reverse

1. Try to replace the motor wiring, or replace the split-phase capacitor, otherwise replace the motor

2. The limit switch is damaged

2. Replacement limit development

3. The limit position is not adjusted

3. Readjust

4. The circuit board is damaged

4. Replace the circuit board

4. The motor runs but the valve does not move

1. The switching mechanism is abnormal

1. Disassembly inspection

2. Connection problems

2. Check the connection

Fifth, do not move manually

1. The switching device is not closed

1. Switching device

2. Mechanical stuck

2. Eliminate the cause of the death

Six, valve stem vibration at startup

The stem nut is loose or improperly tightened

Remove the stem cover or pipe plug and tighten the lock nut

7. Poor insulation

Into the rain (poor sealing of the wire inlet)

1. Repair sealing parts

2. Drying electrical components and motors

3. Pay attention to the cable inlet seal

8. Oil leakage

1. Damaged seal

1. Check and repair the seal

2.The ambient temperature is high, and the internal pressure of the main box increases

2. Loosen the screws that do not affect the work, (preferably oil plug) exhaust

Nine, on-site control is normal, remote control is not

1. The circuit board is damaged

1. Replace the circuit board

2. The control signal line is damaged

2. Check the control signal cable

3. The control signal is connected incorrectly

3. Check the wiring

Ten, on-site control is normal, the remote control valve position display disappears

1. The position sensor is broken

1. Check the sensor

2. Itinerary is not set

2. Reset the itinerary

3. The circuit board is broken

3. Replace the circuit board

11. One-way action

1. Circuit board failure

1. Replace the circuit board

2、One-way limit

2. Re-adjust the limit

3、Damaged motor

3. Replace the motor


Maintenance and maintenance of electric actuators (electric actuators):

Electric actuators (electric actuators) are electromechanical integration products, mainly composed of motors, bearings, gear transmission systems and electronic parts. According to the reliability data published by the US military standard MIL-HDBK-338, mechanical failures of electric actuators (electric actuators) are mainly concentrated on bearings. In terms of electrical appliances, the problem is mainly on the control circuit board, and sometimes the motor also fails. Among the motor failures: winding failure accounts for 20%, bearing failure accounts for 45%, and slip ring, brush, and commutator damage accounts for 5%. Others account for 30%; in bearing failures: lubricant deterioration and disappearance account for 45%, pollution account for 30%, erosion account for 5%, misadjustment accounts for 5%, corrosion accounts for 5%, others account for 10%. It can be seen that good maintenance management can improve the reliability and effectiveness of electric actuators.

1. Strengthen the cleanliness management of lubricating oil The biggest feature of electric actuators is the need to use lubricating oil, whose viscosity changes with oil temperature. If the viscosity is too low, the wear of the transmission components such as the turbine worm and gear will increase, which will reduce the transmission accuracy; if the viscosity is too high, the action will be bad. The management of the cleanliness of lubricating greases is more difficult. The wear of turbine worms and gears, the penetration of impurities and moisture generated by aging, the shedding of internal coatings, and corrosion will affect the cleanliness of lubricating oil.

2. Eliminate the leakage of lubricating grease in time. Due to the high operating frequency and speed of the electric actuator (electric actuator), it is difficult to avoid impact. This is an important reason for the leakage of lubricating grease. Once the lubricating grease leaks, it needs to be resolved in time.

3. Improve the working environment and operating conditions of electric actuators (electric actuators). The reliability and life of electric actuators (electric actuators) are directly related to its use, environment, personnel knowledge and other factors. Only by improving its working environment and conditions of use in maintenance and management, and putting people first, can it extend its service life.

4. Special maintenance should be strengthened in the early stage of the failure. Among all the failures of the electric actuators, the proportion of the initial failures is generally relatively high. Most of the initial faults are caused by preliminary errors in design, manufacturing, and installation. The discovery of these initial faults requires a certain amount of effort, and it takes time to solve them. Therefore, maintenance management should be strengthened during the initial failure period.

5. Do a good job of data management to prevent accidental failures of electric actuators (electric actuators) are generally difficult to predict. In order to prevent sporadic failures, it is necessary to regularly check and maintain, and master the maintenance data and historical file data at a certain stage, which is very important for the accurate implementation of failure judgment and daily maintenance.

6. Improve the professional knowledge of the operation and maintenance personnel The mastery of the professional knowledge of the operation and maintenance personnel directly affects the maintenance management. In recent years, due to changes in the structure of operation and maintenance personnel, they have greatly improved their knowledge and technology of electric actuators. However, many operation and maintenance personnel still lack the professional knowledge and technology they deserve. Most of the on-site operation and maintenance personnel are in a state of "seemingly understand but not understanding" about electric actuators, which is also the weak link of maintenance management. In order to facilitate the operation and maintenance personnel to carry out on-site maintenance and management, we must have advanced awareness in the design of electric actuator systems, fully consider the implementation of maintenance and management, and strive to achieve: the system should be simplified, the simple system failure rate is low, and maintenance management Easy; high degree of standardization, good interchangeability, easy to repair; integration, combination, convenient adjustment and inspection; introduction of new technologies such as fault diagnosis and positioning, fault tolerance/correction.

7. Since the control circuits of electric actuators (electric actuators) are damaged most, it is necessary to increase the service life of the control circuit board, and the control circuit boards of electric actuators (electric actuators) are damaged greatly. Most of them are caused by water ingress or dampness, and the ambient temperature is too high. Therefore, it is necessary to ensure that the electric control room of the electric actuator (electric actuator) is well sealed, and try not to let water get in. Try to make a canopy for the electric actuator (electric actuator) if possible. Most actuators can only reach IP67, this protection can only be drenched in the rain for a short time and cannot be exposed to heavy rain.


主站蜘蛛池模板: 国产精品久久久久久一区二区三区 | 中文字幕在线日韩 | 奇米视频在线观看 | 伊人黄网| 一级片在线观看免费 | 国产高清自产拍av在线 | 国产精品久久久久久久久久久久人四虎 | 秋霞鲁丝无码一区二区三区 | 五月婷婷久久久 | 欧美黑人巨大videos极品 | 欧美成人免费观看全部 | 国产无套白浆一区二区 | 欧洲亚洲天堂 | 亚洲午夜福利精品无码不卡 | 精品久久久久久久久久岛国gif | 亚洲精品视频久久 | 起碰免费公开97在线视频 | 亚洲第一视频在线观看 | 少妇激情a∨一区二区三区 午夜影院一区 | 日本免费一区二区三区四区五六区 | 亚洲精品国产一区二区贰佰信息网 | 欧美毛片无码又大又粗黑寡妇 | 日本美女影院 | 四虎永久在线精品国产免费 | 性无码专区一色吊丝中文字幕 | 色情无码一区二区三区 | 久久摸摸碰碰97网站 | 午夜成人亚洲理论片在线观看 | 国产网曝在线观看视频 | 国产福利啪啪 | 亚洲深夜| 一本一道波多野结衣一区 | 成人精品av一区二区三区 | 区二区三区玖玖玖 | 日日干日日射 | 国产又黄又骚 | 国产成人精品日本亚洲成熟 | 亚洲视频日韩视欧美视频 | 国产精品久久久久久久久久免费 | 麻婆豆传媒一区二区三 | 日韩欧美成人免费观看 | 午夜免费毛片 | 国产一级片免费看 | 99re这里都是精品 | 亚洲精品久久久无码大桥未久 | 国内精品九九久久精品 | 亚洲综合在线观看视频 | 欧美日本韩国亚洲 | 性色a∨人人爽网站hd | 久久久久久曰本av免费免费 | 国产亚洲精品久久7788 | 天天爽天天爽天天爽 | 在线国产网站 | 97caoav| 久草视频福利在线 | 亚洲熟妇无码久久精品 | 亚洲日韩国产二区无码 | 日皮毛片 | 国产精品1卡2卡3卡4卡 | 黑人一级片 | 成年人视频网 | www日韩av| 超薄丝袜足j好爽在线观看 好男人社区www在线官网 | 影音先锋中文无码一区 | 免费国产一区二区三区四区 | 午夜无码性爽快影院6080 | 少妇一边呻吟一边说使劲视频 | 日本高清二区视频久二区 | 少妇情理伦片丰满午夜在线观看 | 亚洲二区在线 | 久久亚洲精品成人av二次元 | 国内精品自在拍精选 | 亚洲国产av最新地址 | 波多野结衣av一区二区无码 | 日本草草影院 | 国产精品久久久久久人妻精品动漫 | а√8天堂中文官网资源 | 老司机亚洲精品影院无码 | 狠狠爱五月丁香亚洲综合 | 四虎精品免费永久免费视频 | 国产69精品久久久久9999apgf | 中文久久久 | 黄网在线观看免费 | 成人一区二区免费视频 | 久久香蕉超碰97国产精品 | 中文字幕人妻伦伦 | 无码孕妇孕交在线观看 | 亚洲综合社区 | 77777av | 精品999久久久 | 久久久www影院人成_免费 | 337p日本大胆欧美裸体艺术 | 韩国午夜理论在线观看 | 久久久久久性高 | a国产在线v的不卡视频 | 中文字幕一区二区视频 | 中文字幕亚洲日韩无线码 | 国产欧美日韩va另类在线播放 | 精品国产综合成人亚洲区2022 |